Fire pump sizing

Fire Pump Capacity Calculator

A fire pump must deliver the design flow at the required head. Enter the flow, the total head, the pump efficiency and a motor sizing margin to get the shaft power, the sized motor power and the next standard motor rating. An indicative planning estimate — it runs entirely in your browser and stores nothing.

Power model: P(kW) = (flow × head) ÷ (6116 × efficiency). The 6116 constant folds in water density and g for flow in L/min and head in m. The motor is sized above shaft power and rounded up to a standard rating.
0.0 kW
Next standard motor rating
0.0 kW
Shaft power
0.0 kW
Motor power (+ margin)
Duty point used
  • Design flow2280 L/min
  • Total head70 m
An NBC / IS fire system is not a single pump — it needs a set: a main electric pump, a standby diesel pump that runs if power fails, and a small jockey pump that holds pressure and stops frequent starts. Each pump must give the rated flow at the rated pressure per its pump curve.

This is an indicative planning estimate, not a compliant fire design or a statutory calculation. The actual pump duty depends on the occupancy classification, the building height, the hydraulic losses of your specific pipework and the AHJ. A licensed fire consultant must design the pump set — against NBC (SP 7:2026) / NBC Part 4 and the relevant IS code (e.g. IS 3844 for hydrants) — and the local fire officer / AHJ signs it off. A wrong pump can mean no water when it matters: verify every figure. Nothing here is a Fire-NOC-ready number.