Amogh N P
 In loving memory of Amogh N P — Architect · Designer · Visionary 
An electrical distribution board with rows of circuit breakers, beside a well-lit modern interior — power and light.
Unit IVBuilding Services - I

Electrical Systems & Lighting Design

Power down the wires, and light by the lumen.

≈ 40 min + worked example

Electricity arrives at high voltage, is stepped down by a transformer, split at the distribution boards and protected by switchgear — and the connected load, times a demand factor below one, gives the maximum demand. Then comes light: sources from the inefficient incandescent to the LED, described by colour temperature and rendering. Learn the supply chain, and the lumen method that turns a required lux level into a number of luminaires.

Learning objectives

By the end of this lesson, you will be able to — mapped to the course outcomes for Design of Structures I:

1
CO4 · Understand

Trace the electrical supply chain from transformer to final circuit.

2
CO4 · Apply

Calculate maximum demand from connected load and demand factor, and convert kW to kVA.

3
CO4 · Understand

Classify light sources by efficacy, colour temperature and colour rendering.

4
CO6 · Apply

Size the lighting for a room by the lumen method.

Supply & switchgear

Power down the wires

Power flows transformer → main panel → distribution boards → final circuits, protected by MCBs (equipment) and RCCBs (people). Maximum demand = connected load × demand factor (< 1); kVA = kW ÷ power factor.[8]

From the grid to the socket HT supply transformer main panel DB DB DB final circuits standby DG set
DiagramThe electrical supply chain: HT supply, transformer, main panel, distribution boards feeding final circuits, with a standby generator

Transformer to circuit

Power arrives as HT/LT supply, a transformer steps it down (e.g. 11 kV → 415/240 V), the main LT panel feeds distribution boards (DBs), and each DB feeds the final sub-circuits. A standby DG set covers mains failure.[8]

Sources & method

Light by the lumen

Sources rank by luminous efficacy (LED ~100–150 lm/W beats incandescent ~15); colour temperature (K, higher = cooler) and CRI are independent. The lumen method sizes the lighting: N = (E·A)/(F·UF·MF).[9, 10]

The lumen method N luminaires of F lumens over area A A N = E · A F · UF · MF E = lux · UF, MF = losses (in the denominator)
DiagramThe lumen method: a room of area A needs illuminance E from N luminaires of F lumens, derated by UF and MF
Colour temperature — higher K is cooler 2700 K warm white 4000 K neutral 6500 K cool daylight warmer / yellower cooler / bluer
DiagramA colour temperature scale from warm 2700 K through neutral 4000 K to cool daylight 6500 K

Efficacy rising

Light sources differ hugely in luminous efficacy (lumens per watt): incandescent ~10–17, CFL ~50–70, fluorescent tube ~50–100, and LED ~80–150+ — which is why LED has displaced the rest. Spectral energy distribution sets a source's colour and rendering.[9]

Light sourceLuminous efficacyNote
Incandescent≈ 10–17 lm/WCheap, warm, CRI ≈ 100, but very inefficient and short-lived.
Halogen≈ 16–24 lm/WAn improved incandescent; crisp white, still inefficient.
CFL≈ 50–70 lm/WCompact fluorescent — efficient, contains mercury, now largely displaced by LED.
Fluorescent tube≈ 50–100 lm/WLinear T8/T5 tubes — long the office workhorse.
LED≈ 80–150+ lm/WThe modern standard — efficient, long-lived, dimmable; efficacy still rising.
Drive the numbers

Lumen-method calculator

Pick a room (which sets the required lux), set the area, lumens per fitting and the loss factors, and read off the number of luminaires. An office of 80 m² at 300 lux, 4000 lm fittings, UF 0.5, MF 0.8 needs 15.[10]

Lumen method · number of luminaires

N = (E·A) / (F·UF·MF) — required lux E = 300. UF and MF are losses, so they sit in the denominator.

0 fittings

Luminaires required

0.0

Exact N

0 lux

Required illuminance

Total flux needed = 24,000 lm on the working plane; round up to whole fittings.

Room / taskTypical luxRange (IS 3646 / NBC)
Corridors / stairs100 lux100–200 lux
Living room (general)150 lux100–200 lux
Kitchen200 lux200–300 lux
Reading / study300 lux150–300 lux
General office300 lux300–500 lux
Drawing office (boards)500 lux500–750 lux
The contrasts

At a glance

AspectOneThe other
Two factorsDemand factor: max ÷ connected (< 1)Diversity factor: Σ maxima ÷ system max (≥ 1)
kW vs kVAkW: real (working) powerkVA: apparent power = kW ÷ power factor
Two protectionsMCB: overload / short-circuit (equipment)RCCB/ELCB: earth-leakage (people)
ColourColour temperature: the white's tone (K)CRI: colour fidelity (0–100) — independent
Lumen-method lossesUF (~0.4–0.6): flux reaching the planeMF (~0.7–0.8): derating for dirt/ageing
Vocabulary

Key terms

Distribution board (DB)

A board of MCBs feeding the final sub-circuits of a zone or floor.

Demand factor

Maximum demand ÷ connected load — always less than one.

Diversity factor

Sum of individual maxima ÷ the coincident system maximum — always ≥ 1.

MCB

Miniature circuit breaker — trips on overload or short-circuit.

ELCB / RCCB

Earth-leakage breaker — trips on a live/neutral imbalance to prevent shock.

Luminous efficacy

Light output per watt (lm/W) — incandescent ~15, LED ~100–150.

Colour temperature

The white's tone in Kelvin; higher K is cooler/bluer (6500 K daylight).

Colour rendering index (CRI)

How faithfully a source renders colour, 0–100; independent of colour temperature.

Lumen method

N = (E·A)/(F·UF·MF) — the calculation that sizes a room's lighting.

Utilisation / maintenance factor

UF (~0.4–0.6) = flux reaching the plane; MF (~0.7–0.8) = derating for dirt/ageing.

Apply it

Worked example

A residence with 10 kW connected load at a demand factor of 0.6 has a maximum demand of 6 kW; at 0.8 power factor that is 7.5 kVA. And a 10 × 8 m office at 300 lux, with 4000-lumen fittings, UF 0.5 and MF 0.8: N = (300 × 80)/(4000 × 0.5 × 0.8) = 24,000/1,600 = 15 luminaires.

Check your understanding

Self-assessment

1. A residence has 10 kW connected load and a demand factor of 0.6. The maximum demand is —

2. Which colour temperature gives the coolest (bluest) light?

3. In the lumen method N = (E·A)/(F·UF·MF), the maintenance factor —

In a nutshell

Recap

Power flows transformer → main panel → distribution boards → final circuits, protected by MCBs (equipment) and RCCBs (people).
Maximum demand = connected load × demand factor (< 1); kVA = kW ÷ power factor.
Light sources rank by efficacy (LED ~100–150 lm/W beats incandescent ~15); colour temperature (K, higher = cooler) and CRI are independent.
The lumen method: N = (E·A)/(F·UF·MF) — required lux and area up top, lumens per fitting and the UF/MF losses below.
The evidence

References & further reading

  1. [8]National Building Code of India (NBC 2016) Part 8 — Building Services (Electrical); National Electrical Code of India / IS 732; IS 3043 (Earthing).
  2. [9]Lighting — luminous efficacy, colour temperature and colour rendering index (lighting design references; CIE).
  3. [10]The lumen method of lighting design and recommended illuminance — IS 3646 (Part 1):1992 / NBC 2016 Part 8; CIBSE.

Further reading

  • NBC 2016 Part 8 and the National Electrical Code of India — building electrical services.
  • IS 3646 (Part 1) — Code of Practice for Interior Illumination.
  • Standard texts on building electrical services and illumination engineering.

Sources gathered and fact-checked June 2026. Published values vary by source, sample and method — treat as indicative and confirm against the cited standard before structural use.