Amogh N P
 In loving memory of Amogh N P — Architect · Designer · Visionary 
Rows of outdoor air-conditioning condenser units on a building, with rooftop cooling towers behind — the heat-rejection side of air-conditioning.
Unit VBuilding Services - I

Air-Conditioning & Fire Protection

The cycle that cools — and the dampers that keep fire out of the ducts.

≈ 40 min + worked example

Air-conditioning controls four things — temperature, humidity, air movement and cleanliness — by running a refrigerant around the vapour compression cycle: the compressor squeezes it, the condenser rejects heat outdoors, the expansion valve drops its pressure, and the evaporator absorbs heat indoors. Learn the cycle, the system types, how to estimate cooling load in tons of refrigeration, and the fire protection an AC system demands.

Learning objectives

By the end of this lesson, you will be able to — mapped to the course outcomes for Design of Structures I:

1
CO5 · Understand

Describe the vapour compression cycle and its four components in order.

2
CO5 · Analyse

Compare the types of AC system — window, split, packaged, central and VRF.

3
CO5 · Apply

Estimate a space's cooling load in tons of refrigeration.

4
CO5 · Understand

Explain the fire protection an AC system requires — fire and smoke dampers.

Vapour compression

The cycle that cools

Compress → condense (reject heat outdoors) → expand (drop pressure) → evaporate (absorb heat indoors). The evaporator does the cooling; the condenser dumps the heat; the expansion valve drops pressure — it does not compress.[11]

The vapour compression cycle compressor condenser (heat out) expansion valve evaporator (heat in / cooling) hot high-P vapour cold low-P refrigerant
DiagramThe vapour compression cycle as a loop: compressor, condenser rejecting heat, expansion valve, evaporator absorbing heat

Four steps, one loop

Air-conditioning controls temperature, humidity, air movement and cleanliness. It runs the vapour compression cycle: compress → condense (reject heat outdoors) → expand (drop pressure) → evaporate (absorb heat indoors) → repeat. Cooling happens at the evaporator (indoors); heat is dumped at the condenser (outdoors).[11]

System types & load

From window unit to chilled-water plant

Systems scale from window/split/packaged (unitary, DX) to a central chilled-water plant and VRF. Capacity is in tons of refrigeration — 1 TR = 3.517 kW = 12,000 BTU/hr.[11, 12]

AC systems — window, split, central Window one box, one room Split indoor + outdoor unit Central chiller AHU AHU chilled water to AHUs
DiagramThree AC systems: a window unit, a split system with indoor and outdoor units, and a central chilled-water plant

Window, split, packaged

Unitary systems are self-contained: a window unit (one box, one room), a split (indoor + outdoor unit, quieter), and a packaged unit (a larger DX unit, often rooftop, ducted to a few spaces). They are simple and cheap but less efficient at scale.[11]

SystemWhat it isBest suited for
WindowA single self-contained unitary box, all components in one casing.One small room — lowest cost; homes, small offices.
SplitAn indoor unit (evaporator + fan) and an outdoor unit (compressor + condenser) joined by refrigerant pipes.Single rooms where a window unit won't fit; quieter.
PackagedA larger self-contained DX unit (often rooftop), ducted to several spaces.Medium buildings — shops, restaurants, small floors.
Central chilled-waterChillers make chilled water, pumped to AHUs/FCUs through piping; water-cooled with a cooling tower.Large buildings — malls, hospitals, hotels, high-rises.
VRF / VRVVariable refrigerant flow — one outdoor unit modulating refrigerant to many indoor units.Modern multi-zone offices needing zoned control without a water plant.
Drive the numbers

Cooling-load calculator

Estimate a space's cooling load in tons of refrigeration from its area and a use factor. A 50 m² office (~538 sqft) at ~120 sqft/TR ≈ 4.5 TR ≈ 15.8 kW — a first cut only; a real calc needs orientation, glazing, occupancy and ventilation.[12]

Cooling load · tons of refrigeration

A first-cut rule of thumb: TR ≈ area(sqft) ÷ (120 sqft/TR). 1 m² = 10.76 sqft; 1 TR = 3.517 kW. A real cooling-load calc needs orientation, glazing, occupancy and ventilation.

0.0 TR

Approx. cooling load

0.0 kW

In kW

0 sqft

Floor area

Rule-of-thumb estimate only — size the actual plant with a full load calculation.

Dampers & shutdown

Fire protection for AC

AC ducts can spread fire and smoke through a building. A fire damper closes on heat (a fusible link melts); a smoke damper closes on a smoke-detector signal; and the fans shut down on alarm.[13]

Fire & smoke dampers in the duct fire-rated wall AC duct fire damper fusible link melts (~74°C) smoke damper closes on a smoke-detector signal Both stop fire and smoke travelling through the ducts; fans shut down on alarm.
DiagramAn AC duct crossing a fire-rated wall with a fire damper that closes on heat and a smoke damper that closes on a smoke signal

The hidden path

An AC system's ducts can carry fire and smoke from room to room and floor to floor — a hidden spread path. So where a duct crosses a fire-rated wall or floor, it must be protected, and on a fire alarm the air-moving fans serving the zone are shut down.[13]

The contrasts

At a glance

AspectOneThe other
Two unitaryWindow: one box in an openingSplit: indoor + outdoor unit, quieter
ScaleUnitary: self-contained, per-roomCentral: one chilled-water plant for the building
Carrying coolingDX: refrigerant at the air coilChilled water: water carries cooling to AHUs/FCUs
Two heatsSensible: changes temperatureLatent: removes moisture (humidity)
Two dampersFire damper: closes on heat (fusible link)Smoke damper: closes on a smoke signal
Vocabulary

Key terms

Vapour compression cycle

Compressor → condenser → expansion → evaporator — the refrigeration cycle of nearly all AC.

Compressor

Raises refrigerant vapour from low to high pressure; the work-input device.

Condenser

Rejects heat outdoors, condensing high-pressure vapour to liquid.

Evaporator

Absorbs heat from the room (the cooling), boiling refrigerant to vapour.

Expansion valve

Throttles the liquid — drops its pressure and temperature (it does not compress).

AHU / FCU

Air handling unit (fan+coil+filter, ducted) / fan coil unit (small per-room terminal).

Cooling tower

Rejects condenser heat to atmosphere by evaporative cooling of water.

Ton of refrigeration (TR)

Cooling capacity unit; 1 TR = 3.517 kW = 12,000 BTU/hr.

Cooling load

The total heat (sensible + latent) to be removed from a space.

Fire / smoke damper

Duct devices closing on heat (fusible link) / on a smoke signal to block fire/smoke spread.

Apply it

Worked example

A 50 m² office = 50 × 10.76 = 538 sqft. At ~120 sqft/TR, cooling load ≈ 538 ÷ 120 ≈ 4.5 TR; in kW, 4.5 × 3.517 ≈ 15.8 kW. Re-run it for a glassy top-floor space (~100 sqft/TR) and a shaded one (~150) to see the spread — then remember a real load calc needs far more than area.

Check your understanding

Self-assessment

1. In the vapour compression cycle, heat is absorbed from the conditioned space at the —

2. One ton of refrigeration equals —

3. A fire damper in a duct typically closes because —

In a nutshell

Recap

AC controls temperature, humidity, air movement and cleanliness via the vapour compression cycle: compress → condense (reject) → expand (drop) → evaporate (absorb).
Cooling is at the evaporator (indoors), heat rejection at the condenser (outdoors); the expansion valve drops pressure, it does not compress.
Systems scale from window/split/packaged (unitary, DX) to a central chilled-water plant and VRF; capacity is in TR (1 TR = 3.517 kW).
AC ducts can spread fire and smoke — fire dampers close on heat (fusible link), smoke dampers on a smoke signal.
The evidence

References & further reading

  1. [11]The vapour compression refrigeration cycle and AC systems (C.P. Arora; Severns & Fellows; ASHRAE Fundamentals).
  2. [12]Ton of refrigeration (1 TR = 3.517 kW = 12,000 BTU/hr) and area-based cooling-load estimation (HVAC references; rule-of-thumb).
  3. [13]Fire and smoke dampers, AHU shutdown and smoke management — NBC 2016 Part 4 (Fire & Life Safety).

Further reading

  • C.P. Arora, Refrigeration and Air Conditioning. McGraw Hill.
  • W.H. Severns & J.R. Fellows, Air Conditioning and Refrigeration. John Wiley.
  • ASHRAE Handbook — Fundamentals; NBC 2016 Part 4.

Sources gathered and fact-checked June 2026. Published values vary by source, sample and method — treat as indicative and confirm against the cited standard before structural use.